HR Unit PCB
- 76 -
Copyright © 2020 LG Electronics Inc.
All rights reserved. Only training and service purposes.
2. Automatic Addressing
DIP-SWITCH
7 - Segment
SW01C (
Ɨ
: confirm)
SW02C (
ȭ
: backward)
SW03C (
ȯ
: forward)
SW04C ( × : cancel)
SW01D (reset)
The address of indoor units would be set by Automatic Addressing
- Wait for 3 minutes after supplying power.
(Master and Slave outdoor units, indoor units)
- Press RED button of the outdoor units for 5 seconds. (SW01C)
- A “88” is indicated on 7-segment LED of the outdoor unit PCB.
- For completing addressing, 2~7 minutes are required depending on numbers of connected indoor units
- Numbers of connected indoor units whose addressing is completed are indicated for 30 seconds on 7-segment
LED of the outdoor unit PCB
- After completing addressing, address of each indoor unit is indicated on the wired remote control display win-
dow. (CH01, CH02, CH03, ……, CH06 : Indicated as numbers of connected indoor units)
CAUTION
• In replacement of the indoor unit PCB, always perform Automatic addressing setting
again (At that time, please check about using Independent power module to any
indoor unit.)
• If power supply is not applied to the indoor unit, operation error occur.
• Automatic Addressing is only possible on the master Unit.
• Automatic Addressing has to be performed after 3 minutes to improve communica-
tion.