Self-diagnosis function
Display
Title
Cause of Error
Outdoor unit related error
1
1
3
Outdoor Unit Liquid pipe Temperature Sensor
Error
Liquid pipe temperature sensor of Outdoor Unit is
open or short
1
1
5
Outdoor Unit Subcooling Outlet Temperature
Sensor Error
Outdoor Unit Subcooling Outlet Temperature
Sensor Error
1
5
0
Outdoor Unit Discharge Super
Heat Low
Outdoor Unit LowDischarge Super
Heat for 5 minutes
1
5
1
Failure of operation mode conversion at
Outdoor Unit
Failure of operation mode conversion at Outdoor
Unit
HR unit related error
2
0
0
1
Searching pipe Error
Failure of automatic addressing of valves
2
0
1
C +
#HR
HR unit1 Liqiud sensor error
Liquid pipe sensor of HR unit open or short
2
0
2
C +
#HR
HR unit1 Sub Cooling Pipe In sensor error
Sub Cooling Pipe In sensor of HR unit open or
short
2
0
3
C +
#HR
HR unit1 Sub Cooling Pipe Out sensor error
Sub Cooling Pipe Out sensor of HR unit. open or
short
2
0
4
C +
#HR
Communication error
Failing to receive HR unit signal at outdoor unit
2
0
5
C +
#HR
Communication error between HR unit and the
upgraded 485 modem.
4 series upgraded 485 communication error
between HR unit and HR unit modem
2
0
6
C +
#HR
Duplicate address error of HR unit
When the HR unit address is set duplicated at the
4 series upgraded 485 communication
2
0
7
C +
#HR
Communication error between Master and
Slave Main PCB of HR Unit
When fail to communication between Master and
Slave Main PCB of HR Unit
2
0
8
C +
#HR
Communication error of EEPROM of HR Unit
When fail to communication of EEPROM of HR
Unit
C : HR unit
# : HR unit Number
# HR is the information in outdoor unit Main PCB segment
(HR unit is excluded from #HR related display on PCB segment)
CAUTION
• To use open line 485 communication (9,600 bps communication), you need to use a product in which all of the indoor
unit/HR unit/outdoor unit/accessory model can use (9,600 bps communication).