Self-diagnosis function
Error diagnosis and countermeasure flow chart
Check liquid bypass
1. Individual power of indoor unit is open during operation
2. Indoor unit EEV fault(ref. leak much)
3. Indoor unit EEV connector disconnected.
4. SC EEV fault(ref. leak much)
5. Liquid pipe – gas pipe direct connection
Error No.
Error Type
Error Point
Main Reasons
Discharge superrheat
is under 3 ℃
(liquid back)
Discharge
superheat low
CH1501
Is there indoor unit
which leaks ref. much
1)
?
Is SC EEV or
SC circuit leaks?
Is EEV head(Coil)
assembly normally?
Change SC EEV or
SC EEV assembly
Assemble again or
change EEV head(coiL)
Change EEV assembly
Yes
Yes
Yes
Is EEV connector
connected normally?
1)
Ref. leakage much
: Both Pipe in, pipe out temp. is under 10 ℃ during unit is off(EEV 40 pls)
Also, big refrigerant flow noise occured
Yes
No
Check liquid pipe - gas
pipe direct connection
No
Connect EEV connector
No