Self-diagnosis function
1. 130 % more than outdoor unit rated capacity
2. Wrong connection of transmission cable/pip-
ing
3. Detect ot outdoor unit PCB
Error
No.
Error Type
Error Point
Main Reasons
Sum of indoor unit capaci-
ty exceed outdoor unit
capacity specification
Over-Capacity
(Sum of indoor unit capaci-
ty is more than outdoor
capacity)
51
n
Error diagnosis and countermeasure flow chart
Is capacity sum of
indoor units less than
130 % of outdoor unit
capacity at LGMV?
No
Yes
Are quantity and capacity
of indoor units installed
same as the data of LGMV?
Yes
Adjust the capacity of indoor
and outdoor unit
No
Check communication cables
between indoor and outdoor
units
End