- 101 -
Copyright © 2020 LG Electronics Inc.
All rights reserved. Only training and service purposes.
Self-diagnosis function
Display
Title
Cause of Error
Outdoor unit related error
3
6
Outdoor Unit Low Compression Ratio
Limited
Outdoor Unit Low Compression Ratio Limited
4
0
Outdoor Unit Inverter Compressor CT
Sensor Fault
Outdoor Unit Inverter Compressor CT Sensor open or short
4
1
Outdoor Unit Inverter Compressor1
Discharge Temperature Sensor Fault
Outdoor Unit Inverter Compressor Discharge Temperature
Sensor open or short
4
2
Outdoor Unit Low Pressure Sensor Fault
Outdoor Unit Low Pressure Sensor open or short
4
3
Outdoor Unit High Pressure Sensor Fault
Outdoor Unit High Pressure Sensor open or short
4
4
Outdoor Unit Air Temperature Sensor Fault
Outdoor Unit Air Temperature Sensor open or short
4
5
Outdoor Unit Heat Exchanger Temperature
Sensor (Front side) Fault
Outdoor Unit Heat Exchanger Temperature Sensor(Front side)
open or short
4
6
Outdoor Unit Suction Temperature Sensor
Fault
Outdoor Unit Suction Temperature Sensor open or short
5
0
Omitting connection of R, S, T power of
Outdoor Unit
Omitting connection of outdoor unit
5
1
Excessive capacity of indoor units
Excessive connection of indoor units compared to capacity of
Outdoor Unit
5
2
Communication error : inverter PCB
→
Main
PCB
Failing to receive inverter signal at main PCB of Outdoor Unit
5
3
Communication error : indoor unit
→
Main
PCB of Outdoor Unit
Failing to receive indoor unit signal at main PCB of Outdoor
Unit .
5
7
Communication error : Main PCB
→
inverter PCB
Failing to receive signal main PCB at inverter PCB of Outdoor
Unit
6
0
Inverter PCB EEPROM Error of Outdoor
Unit
Access Error of Inverter PCB of Outdoor Unit
6
2
Outdoor Unit Inverter Heatsink High
Temperature
System is turned off by Outdoor Unit Inverter Heatsink High
Temperature
6
5
Outdoor Unit Inverter Heatsink Temperature
Sensor Fault
Outdoor Unit Inverter Heatsink Temperature Sensor open or
short
6
7
Outdoor Unit Fan Lock
Restriction of Outdoor Unit
7
1
Converter CT Sensor Error of Outdoor Unit
Converter CT Sensor Error of Outdoor Unit
8
6
Outdoor Unit Main PCB EEPROM Error
Communication Fail Between Outdoor Unit Main MICOM and
EEPROM or omitting EEPROM