Functions
- 53 -
Copyright © 2020 LG Electronics Inc.
All rights reserved. Only training and service purposes.
Are whole indoor units
operating
cooling mode?
Solenoid valve open
for liquid bypass
(High pressure gas
→
Low pressure gas valve)
Indoor units operating
Yes
No
2.1 Oil Return/Defrost Control
2.2 Liquid Bypass Control
2.3 Subcooling EEV Control
Target : about 25 ℃(77 ℉)
Subcooling EEV works with Fuzzy rules to keep the degree of subcooling at the outlet of subcooler during
simultaneous operation
The degree of subcooler = T outlet of subcooler – T inlet of subcooler
2. Special Control
Component
Starting
Running
Ending
Inverter compressor
Stop
60 Hz
40 Hz
High pressure gas valve
Keep
Close
Open or Close
Low pressure gas valve
Keep
Open
Open or Close
Balancing valve
Open for 30s
Close
Close