Self-diagnosis function
n
Error diagnosis and countermeasure flow chart
Is temperature sensor
connector connections
are normal?
Is the value of temperature
sensor resistance normal?*
Check and correct connection
Replace sensor
Replace outdoor unit PCB
Yes
Yes
No
No
* Sensor resistance 100 kΩ over (open) or 100 Ω below (short) will generate error
Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance value
according to outdoor unit temperature by referring below table (±5 % tolerance)
Air temperature sensor: 10 °C = 20.7 kΩ : 25 °C = 10 kΩ : 50 °C= 3.4 kΩ
Pipe temperature sensor: 10 °C = 10 kΩ : 25 °C = 5 kΩ : 50 °C= 1.8 kΩ
Error No.
Error Type
Error Point
Main Reasons
65
Outdoor unit liquid
pipe (condenser) tem-
perature sensor error
Abnormal sensor resis-
tance value
(Open/Short)
1. Defective temperature sensor connection
2. Defective temperature sensor (Open / Short)
3. Defective outdoor unit PCB