Self-diagnosis function
67
Fan Lock Error
Error No.
Error Type
Error Point
Main Reasons
Fan RPM is 10RPM or less
for 5 seconds when ODU
fan starts or 40 RPM or
less after fan starting.
1. Fan motor defect / assembly condition
abnormal
2. Wrong connection of fan motor connector
3. Reversing rotation after RPM target apply
4. Inv. PCB assembly defect
5. Fan lock by Heavy Snowfall.
n
Error Diagnosis and Countermeasure Flow Chart
Is ODU Fan Motor Assemble
condition normal?
No
Yes
Recheck power and installation condition
Check ODU Fan Motor assemble condition and fan locking
→
Reassemble or replace if abnormality found
Is ODU Fan Motor normal?
No
Yes
1. Check resistance between each phase(U,V,W) of ODU
fan motor terminal (16.8 Ω ±5 % at 75 °…)
2. Check insulation resistance between ODU fan motor
terminal(U,V,W)
→
Replace fan motor if abnormality found
Is wire connection of
ODU Fan Motor wire normal?
No
Yes
Check wiring between ODU fan motor and Inv. PCB
(Check if and Motor output terminal color is matched)
→
Reassemble if abnormality found
Is Inv. PCB assembly normal?
No
Yes
Replace Inv. PCB assembly
* Inv. PCB
Fan1
Fan2