Self-diagnosis function
3. Self-diagnosis function
Error Indicator
- This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
- Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of
outdoor unit control board as shown in the table.
- If more than two troubles occur simultaneously, lower number of error code is first displayed.
- After error occurrence, if error is released, error LED is also released simultaneously.
Error Display
1st,2nd,3rd LED of 7-segment indicates error number, 4th LED indicates unit number.
Ex)
No. of Error Compressor
Error No.
No. of Error Unit
Repeat
Display
Title
Cause of Error
Indoor unit related error
0
1
Air temperature sensor of indoor unit
Air temperature sensor of indoor unit is open or short
0
2
Inlet pipe temperature sensor of indoor unit
Inlet pipe temperature sensor of indoor unit is open or short
0
3
Communication error : wired remote
controller
↔
indoor unit
Failing to receive wired remote controller signal in indoor unit
PCB
0
4
Drain pump
Malfunction of drain pump
0
5
Communication error : outdoor unit
↔
indoor unit
Failing to receive outdoor unit signal in indoor unit PCB
0
6
Outlet pipe temperature sensor of indoor unit
Outlet pipe temperature sensor of indoor unit is open or short
0
9
Indoor EEPROM Error
In case when the serial number marked on EEPROM of
Indoor unit is 0 or FFFFFF
1
0
Poor fan motor operation
Disconnecting the fan motor connector/Failure of indoor fan
motor lock
Outdoor unit related error
2
1
Outdoor Unit Inverter Compressor IPM Fault
Outdoor Unit Inverter Compressor Drive IPM Fault
2
2
Inverter Board Input Over Current(RMS)
of Outdoor Unit
Outdoor Unit Inverter Board Input Current excess (RMS)
2
3
Outdoor Unit Inverter Compressor DC link
Low Voltage
DC charging is not performed at Outdoor Unit after starting
relay turn on.
2
4
Outdoor Unit High Pressure Switch
System is turned off by Outdoor Unit high pressure switch.
2
5
Outdoor Unit Input Voltage High/ Low Voltage Outdoor Unit input voltage is over 487 V or below 270 V
2
6
Outdoor Unit Inverter Compressor Start
Failure
The First Start Failure by Outdoor Unit Inverter Compressor
Abnormality
2
9
Outdoor Unit Inverter Compressor Over
Current
Outdoor Unit Inverter Compressor Fault OR Drive Fault
3
2
Outdoor Unit Inverter Compressor1 High
Discharge Temperature
Outdoor Unit Inverter Compressor1 High Discharge
Temperature
3
4
High Pressure of Outdoor Unit
High Pressure of Outdoor Unit
3
5
Low Pressure of Outdoor Unit
Low Pressure of Outdoor Unit