- 52 -
Copyright © 2020 LG Electronics Inc.
All rights reserved. Only training and service purposes.
Functions
1.1 Normal Operation
1.2 Starting Control(Heating Mode Only)
If the system is operated in the heating mode, all high pressure gas valves are opened
1.3 Valve Control
Mode change timer is calculated as Table 1, and valves are controlled by Mode change timer according to
Table 2.
Table 1. Mode change timer calculation
1. Basic Control
Functions
Actuator
Power on
Cooling operation
Heating operation
Stop state
High pressure gas valve
Close
Close
Open
Keep
Low pressure gas valve
After 30 seconds
Open
Open
Close
Keep
Liquid valve
Close
Open
Close
Close
Operating mode
Mode change
timer
H/P gas valve
L/P gas valve
Balancing valve
Cooling
120 ≤ timer
Keep
Keep
Close
0 < timer < 120
Close
Close
Open
timer = 0
Close
Open
Close
Heating
180 ≤ timer
Keep
Keep
Close
0 < timer < 180
Close
Close
Close
timer = 0
Open
Close
Close
Stop or ventilation
0 < timer < 5
Cooling mode :
Close
Keep
Close
Timer = 0
Heating mode : Low
pressure gas valve
➔
Close
Keep
Close
Previous mode
Changing mode
Mode change timer
Stop or ventilation
Cooling or heating
120 seconds
Cooling mode
Heating
180 seconds
Heating mode
Cooling
120 seconds
Cooling or heating
Stop or ventilation
During heating : 60 seconds
During cooling : 0 seconds
Table 2. Valve control by mode change timer