4.2 Pump Down
This function gathers the refrigerant present in the system to ODU
Use this function to store refrigerant of system in ODU for leakage or IDU replacement.
[Note]
If low pressure become under 307 kPa (blink), close the gas SVC V/V of all ODU immediately.
If low pressure descends below 229 kPa, the system turns off automatically. Close the gas SVC V/V immediately.
Caution
1.Use pump down function within guaranteed temperature range
IDU : 20~32 °C(68~89.6 °F)
ODU : 5~40 °C(41~104 °F)
2. Make certain that IDU doesn't run with thermo off mode during operation
3. Maximum operation time of pump down function is 30 min.
(in case low pressure doesn't go down)
Power Reset after Master Unit
DIP switch setting (Refer to DIP switch setting page )
All IDU cooling operation
Press the red button (SW01C)
*Current low
pressure
*Current low
pressure
*Current low pressure
under 307 kPa(44.5 psi)
(blink)
Note 1)
Note 2)
Yes
Low pressure
< 229 kPa(33.2 psi)
IDU, ODU OFF
Power reset after DIP switch off
Pump down completed
Press the red button
(SW01C)
Satisfy low
pressure target?
[Case 1] ODU Service Valve Setting
(for Heat Recovery System)
[Case 2] ODU Service Valve Setting
(for Heat Pump System)
[Case 1] ODU Service Valve Setting
(for Heat Recovery System)
[Case2] ODU Service Valve Setting
(for Heat Pump System)
Setting method
No
Close liquid service valve of each unit.
Refer the right side figures of this page and
open the proper valve by each system.
Liquid
Pipe
Close
Open
Close
Close
Close
Close
Close
Close
Close
Close
Open
High pressure
Gas Pipe
Low pressure
Gas Pipe
Liquid
Pipe
No used
(Keep closed)
Gas
Pipe
Liquid
Pipe
No used
(Keep closed)
Gas
Pipe
Liquid
Pipe
Low pressure
Gas Pipe
High pressure
Gas Pipe
Close
Function