- 124 -
Copyright © 2020 LG Electronics Inc.
All rights reserved. Only training and service purposes.
Self-diagnosis function
40
Inverter compressor CT
sensor error
Error
No.
Error Type
Error Point
Main Reasons
Micom input voltage isn't
within 2.5 V ±0.3 V at initial
state of power supply
1. Input voltage abnormal (L1(L) – L2(N))
2. ODU Inv. PCB damage
(CT sensing part)
n
Error Diagnosis and Countermeasure Flow Chart
* Measuring input voltage
Is input voltage normal?
No
Yes
Recheck power and installation condition
Check
L1(L) – L2(N) phase voltage is 208 V(±10 %) or 230 V(±10 %)
→
Check connection condition and wiring if power is
abnormal
Is inverter PCB assembly normal?
No
Yes
Replace inverter PCB assembly