HR Unit PCB
- 75 -
Copyright © 2020 LG Electronics Inc.
All rights reserved. Only training and service purposes.
2) Zoning setting
Note:
Use the Zoning Control when install two or more indoor units at 1 branch of HR Unit. The indoor units controlled by
Zoning Control can be selected collectively as the cooling/heating mode.
SW01E
SW #1 On : Select Valve #5
Slave
ON
OFF
SW02B
SW01B
SW01C
After selecting No.1 zoning
indoor unit, input the central
control address of indoor unit.
Slave
After selecting No.2 zoning
indoor unit, input the central
control address of indoor unit.
Setting SW01C to ‘0’
After selecting No.3 zoning
indoor unit, input the central
control address of indoor unit.
SW01E
SW #1 Off : Finish Valve #5
Slave
ON
OFF
SW01E
SW #2 On : Select Valve #6
Slave
ON
OFF
SW02B
SW01B
Input the central control
address of Indoor unit
Slave
SW01E
SW #2 Off : Finish Valve #6
Slave
ON
OFF
0
SW02B
SW01C
SW01B
Slave
1
SW01C
Slave
0
SW02B
SW01C
SW01B
Slave
2
ex) Manual pipe detection of Valve #5 with three zoning indoor units, #6 without zoning unit.