Terminate inverter’s AC output wires inside the AC disconnect or wiring box.
-
Connect the Neutral wire to the terminal (
b
).
-
Connect L1 wire to the terminal (
a
)
-
Connect L2 wire to the terminal (
c
)
-
Use a 1/8” (3.5 mm) flat blade screwdriver to tighten the screw terminal to 10.5 in-lbs (1.2
Nm) of torque for all above connections.
NOTICE
Stranded copper wire should be checked so that all strands go into the terminal opening.
NOTICE
If the grid type with Neutral connection is selected, please double check whether the Neutral wire
is connected reliably. An unsuccessful Neutral wire connection will make the unit fail to feed in
power to the grid because of the wrong phase voltage detection.
B- A+EN GND
B-
A+
EN
GND
B- A+EN GND
B-
A+
Battery pack
communications
Energy meter
communications
< Wiring box full connection >