Installation
36
Install
ation
2
Power Status LED
LED
LED color
Function
Indication
Troubleshooting
RUN
Green
Flashing ON/OFF
(for 1 second)
Working normally
Red
ON for > 3 seconds
Internal error
Contact support
Yellow
Flashing ON/OFF
(for 1 second)
No communication
Check that the
communication wires are
connected correctly.
Phase Status LED
LED
LED
color
Function
Indication
Troubleshooting
RUN
Green ON for > 3 seconds
No current
Flashing ON/OFF
(for 1 second)
Positive power
Red
Flashing ON/OFF
(for 1 second)
Negative power
Check for reversed CTs,
swapped CT wires, or CTs
not matched with the lines.
Flashing with green LED
High voltage > 130 V
Check the line voltages
and the meter rating.
Flashing with yellow LED
Low voltage < 70 V
Yellow
Flashing ON/OFF
(for 1 second)
Break fault < 70 V
ON for > 3 seconds
Frequency is below
45 Hz or above 70 Hz
Check for the presence of
high noise.
Содержание A005KEEN261