Utility AC voltage
The LG Electronics ESS inverters are grid-tied to the public utility. The inverters are software
configurable via the user display panel for various 208 V AC or 240 V AC 60 Hz public utility grids.
CAUTION
The LG Electronics ESS Inverters should never be connected to a 120 V AC utility service. NEC
705.12 requires that the inverter be connected to a dedicated circuit with no other outlets or
devices connected to the same circuit.
AC connection voltage and frequency limits:
Voltage range for 208 V nominal, line to line
185 V - 226 V
Voltage range for 240 V nominal, line to line
213 V - 262 V
Frequency Range
59.3 Hz - 60.5 Hz
Public grid configuration allowed:
< 240 V / 120 V Split Phase AC Grid >
< 208 V Inverter AC Grid >