Installation
15
Install
ation
2
Installation location
y
Install the inverter on a non-flammable support base.
y
The inverter must be mounted vertically on a flat surface.
y
A minimum distance of 6” (15.2 cm) of unobstructed clearance between the inverter and
other equipment and 4” (10 cm) between the inverter and a corner is required to promote free
convection.
y
Ensure the mounting hardware and structure can support the weight of the inverter.
y
Ensure the mounting hardware meets the appropriate building code.
y
Avoid installation on resonating surfaces (light construction walls etc.).
y
Installation can be indoors or in protected outdoor areas.
y
Avoid direct sun exposure.
y
Ensure ambient temperature is within -22 °F to +149 °F (-30 °C to +65 °C) for optimal
efficiency of the system.
y
Despite having a Type 4 enclosure with a soiling category III certification, the inverter must not be
exposed to heavy soiling.
y
Unused connectors and interfaces must be covered through sealing connectors.
< Mounting directions >
Please make sure the inverter is installed vertically, especially if it is to be installed outdoors.