Installation
39
Install
ation
2
< Wiring box AC assembly – terminal labeling >
a
L1 Terminal
b
N Terminal
c
L2 Terminal
d
Ground
WARNING
An AC disconnect may be required by your local AHJ. Please check local regulations to determine if
an AC disconnect is required for your installation.
NOTICE
Stranded copper wire should be checked so that all strands go into the terminal opening.
A
Mount the AC disconnect (if required by local AHJ) close enough to the inverter.
B
Install conduit fitting and conduit into the wiring box compartment from AC disconnect or utility
service panel.
C
Loosely fit the conduit into the inverter's open conduit fitting and the DC disconnect or wiring
box conduit fitting and then thread the inverter's AC output wires through the conduit.
D
Route AC wiring through conduit and verify that the exposed wires are at least 6” (15.24 cm)
in length to provide adequate strain relief and wire end strip length required. Secure the conduit
into both fittings, then tighten conduit fittings to the manufacturer's recommended torque.