Installation
32
Install
ation
2
Battery pack connections
Connection Power / Communication cables, according to the labels marked.
INFO
y
Commissioning should be within 180 days of manufacture date. Verify this via the unit
serial number.
y
Battery cables are recommended to be 12 – 8 AWG.
a
b
c
A
Connect the power cables to the
corresponding terminals.
a
Ground terminal
b
Negative (-) teminal
c
Positive (+) terminal
Power terminal block
(+)
(-)
GND
y
Max cable length: 10 m (35 ft.)
y
Cable Type: 4-10 mm
2
(12 – 8 AWG)
y
DC600 V insulated
abcd
B
Connect the communication cables to the
corresponding terminals.
a
Ground terminal(GND)
b
ENABLE_High terminal (EN)
c
RS485_High terminal (A+)
d
RS485_Low terminal (B-)