Message
Category
LED Signals
Message Explanation
Example
LED
Color
Status
Behavior
INFO LED
Firmware upgrade
INFO
Yellow
<BLINK>
1s on, 1s off
Firmware upgrading is ongoing
Reset button is
pressed
INFO
Green
<BLINK>
Varied behavior
When reset button is pressed
for different time duration, the
blinking behavior is different,
and after releasing the button,
different actions will be
executed.
[1] Press time duration: < 2.5 s
Blink behavior: constantly on
Action: No action
[2] Press time duration:
2.5 - 9.5 s
Blink behavior:
0.2 s on, 0.2 s off
Action: Clear ARC fault
[3] Press time duration:
9.5 - 16.5 s
Blink behavior:
0.4 s on, 0.4 s off
Action: Gateway reset
[4] Press time duration: > 16.5 s
Blink behavior: 1 s on, 1 s off
Action: Delta reserved
Notes:
y
Action will not be executed
3 s later after the button
is released. If the button is
pressed again within 3 s,
the former action will be
cancelled and start triggering
of new expected action.
y
LED indication behavior will
be ended after 5 s later after
the button is released.
LED signals:
INFO LED is blinking with Green,
and 0.2 s on and 0.2 s off
Message:
Reset button is clicked for
more than 2.5 s and less than
9.5 s, and if release the button,
ARC fault clear action will be
executed
Receiving image
INFO
Green
<BLINK>
1s on, 1s off
Inverter is receiving image file
Equipment alarm
INFO
Yellow
<ON>
constantly on
External event occurs and
inverter is unable to run
FAULT LED
Arc fault
FAULT
Red
<ON>
constantly on
Arc fault occurs
Ground fault
FAULT
Red
<BLINK>
1s on, 1s off
Ground fault occurs
Others
Initialization
OPER
Green
<ON>
On until done
Inverter initialization after
powering on AC
BAT
Green
<ON>
On until done
COMM Green
<ON>
On until done
INFO
Green
<ON>
On until done