Chapter 3: Installing NE0152T Hardware and Options
43
6.
Attach the filler plate (Item 9) and rear mounting brackets to the rear rack posts
with M6 screws (Item 3),and either clip nuts (Item 4) or cage nuts (Item 5). Torque
the screws to approximately 5.7 Nm ± 0.1 Nm (50 inch-pounds).
7.
Secure the rear brackets to the front brackets with M3.5 screws (Item 6). Torque the
screws to approximately 0.5 Nm (4 inch-pounds).
8.
If installing the 1U air-duct option, see the instruction on
9.
Connect all external cables in accordance with the
10.
Initialize the switch. See
Chapter 5, “Initializing the NE0152T“
11.