HEATING OPTION
e-BALTIC-IOM-2020.12-EN
72
SAFETY INSTRUCTIONS
FUEL:
Before starting up the heater, make sure that:
•
The gas mains supply data is compatible with the data stated on the nameplate;
•
The combustion air intake ducts (when fitted) and the fume exhaust pipes are those specified by the manufacturer;
•
The combustion air is supplied in such a way to avoid even partial obstructions of the intake grille (caused by leaves
etc.);
•
The fuel intake internal and external seal is checked during the testing stage, as required by applicable standards;
•
The heater is supplied with the same type of fuel it has been designed for;
•
The system is correctly sized for such flow rate and is fitted with all safety and monitoring devices required by applicable
standards;
•
The inside of the gas pipes and air distribution ducts for ducted heaters has been thoroughly cleaned;
•
The fuel flow rate is suitable for the power required by the heater;
•
The fuel supply pressure is between the range specified on the nameplate.
GAS LEAKS
If you smell gas:
•
Do not operate electrical switches, telephones or any other object or device that could produce sparks;
•
Immediately open doors and windows to create an air flow to vent the gas out of the room;
•
Close the gas valves;
•
Call for qualified staff.
PRODUCT RANGE
DESCRIPTION
UNIT
C
D
E
E+
F
G
H
Systema’s Goods
EOLO
LXC 50
EOLO
LXD 70
EOLO
LXE 90
EOLO
LXE+ 110
EOLO
LXF 130
EOLO
LXG 170
EOLO
LXH 230
NOMINAL HEAT INPUT (NCV)
kW
50
70
90
110
130
170
230
MIN HEAT OUTPUT (NCV)
kW
10
14
18
22
26
34
46
EFFICIENCY AT NOMINAL
HEAT INPUT
%
96
96
96
96
96
96
97
EFFICIENCY AT MINIMAL
HEAT INPUT
%
109
109
109
109
109
109
109
Nominal gas
consumption at 15°C
and 1013 mbar
G20
m
3
/h
5.29
7.41
9.52
11.64
13.76
17.99
24.34
G25
m
3
/h
6.15
8.62
11.08
13.54
16.00
17.99
28.31
G30
kg/h
3.94
5.52
7.10
8.67
10.25
13.41
18.14
G31
kg/h
3.88
5.44
6.99
8.55
10.10
13.21
17.87
Supply pressure
G20
mbar
20
20
20
20
20
20
20
G25
mbar
25
25
25
25
25
25
25
G30
mbar
37
37
37
37
37
37
37
G31
mbar
37
37
37
37
37
37
37
Gas inlet connection
inch
3/4"
3/4"
3/4"
3/4"
1"
1"1/4
1"1/4
Chimney outlet diameter
mm
100
100
100
100
130
130
150
Max length of gas exhaust
pipe
m
5
5
5
5
5
5
5
Power supply
V/Hz
2/PE
R
400/50
Nominal electrical power
kW
65
135
173
170
180
250
250
Operation temperature
°C
-20 to 40
Net weight
kg
100
120
155
155
195
260
310