FILTERS
e-BALTIC-IOM-2020.12-EN
61
FILTERS
FILTER REPLACEMENT
After opening the filter access panel, lift the filter retaining log.
The filters can then be removed and replaced easily by sliding the
dirty filters out and clean ones in.
The CLIMATIC controller monitors the pressure drop across the
filter.
The following set points can be adjusted depending on the installation.
•
“Airflow” in menu 2333 = 25 Pa by default
•
“No filter “ in menu 2334 = 50 Pa by default
•
“Dirty Filter” in menu 2335 = 250 Pa by default
The actual pressure drop measured across the coil can be read on the Climatic Display DS in menu 2332.
The following faults may be identified
•
Fault code (1) Blower, Flow Switch Cut Off, if measured ΔP across the filter and coil is below the value set in menu 2333
•
Fault code (4) Blower, Filters, Dirty if measured ΔP across the filter and coil is above the value
set in menu 2335
•
Fault code (5) Blower, Filters, Missing, if measured ΔP across the filter and coil is below the value set in menu 2334
BE CAREFUL:
Choose the filters' fire classifications according to the local regulations
BE CAREFUL:
Please perform a leak detection.
Please note that filters can generate static electricity and are potentially flammable.