INSTALLATION ON A ROOFCURB
e-BALTIC-IOM-2020.12-EN
36
CURBING AND FLASHING
Check that the insulation is continuous, counter flash and seal around the frame as shown
CAUTION: To be effective, the upstream must end below the drop edge. Where pipes and electrical conduits extend through
the roof, flashing must conform to local codes of practice
Before installing the equipment, make sure that seals are not damaged and check that the unit is secured to the mounting
frame. Once in position, the bottom of the equipment must be horizontal. The installer must comply with local authority
standards and specifications.
* Check that the roofcurb height is enough to respect a sealing height of 150mm minimum (French DTU 43.3) considering the
building specifications: geometry of the roof, material and thickness of the insulations and other protection layers, slope of the
roof…).
Gasket
Rooftop
Sealing / fire bulkhead
Insulation
Roofcurb
Siding
Building frame