FLAMMABLE GASES
e-BALTIC-IOM-2020.12-EN
18
MEANING OF LEDS
The alarm relay is used to raise the presence of gas. The fault relay is used to detect the presence of a fault on the sensor.
Start up and normal operation
LED
Analog output
Relay
Power
Alarm
Default
Alarm
Default
Start-up
Diagnostic (0.5sec)
< 2 mA
OFF
Fault
4
Preheat
< 2 mA
OFF
Fault
4
Normal operation
2
4 -20 mA
1
3
OK
5
Specific operations or alerts
LED
Analog output
Power
Relay
Power
Alarm
Default
Alarm
Default
Maintenance message
2
4 -20 mA
1
3
OK
5
Special mode
6
7
2 mA
7
Fault
4
Fault detected
6
7
2 mA
7
Fault
4
Processor failure
< 1 mA
OFF
Fault
4
Bump test
LED
Analog output
Power
Relay
Power
Alarm
Default
Alarm
Default
Normal operation
2
4 -20 mA
1
3
OK
5
Press the test button
for 20 seconds
Bump test
20 mA
OFF
OK
5
Release the test button
Normal operation
2
4 -20 mA
1
3
OK
5
1
The status depends on the concentration of the gas measured.
2
The status depends on the concentration of the gas measured and the alarm threshold.
3
The status depends on the concentration of the gas measured, the alarm threshold and the operating mode.
4
Relay deactivated, contact open.
5
Relay activated, contact closed.
6
LED cyclically flashing during message sending.
7
Previous status does not change.