HEATING OPTION
e-BALTIC-IOM-2020.12-EN
71
CONDENSING GAS BURNER
PRELIMINARY CHECKS BEFORE START-UP
NOTE :
ANY WORK ON THE GAS SYSTEM MUST BE CARRIED OUT BY QUALIFIED PERSONNEL.
THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH LOCAL SAFETY CODES AND REGULATIONS AND CAN ONLY BE USED
IN PLANED INSTALLATION CONDITIONS FOR OUTDOOR.
PLEASE READ CAREFULL
Y THE MANUFACTURER’S
INSTRUCTIONS BEFORE STARTING A UNIT.
BEFORE COMMISSIONING A UNIT WITH GAS BURNER, IT IS MANDATORY TO ENSURE THAT THE GAS DISTRIBUTION
SYSTEM (TYPE OF GAS,
AVAILABLE PRESSURE…)
IS COMPATIBLE WITH THE ADJUSTMENT AND SETTINGS OF THE UNIT.
THE GAS MODULE SAFETY CHAIN MUST BE CHECKED BY A PROFESSIONAL BEFORE START-UP OF THE PRODUCT.
CHECK ACCESS AND CLEARANCE AROUND THE UNIT
•
Make sure one can move freely around the unit.
•
A minimum one-meter clearance must be left in front of the burnt gas exhaust flue.
•
Combustion air inlet and burnt gas exhaust(s) must not be obstructed in any way.
•
Depending on the operating conditions (prevailing winds), it may be necessary to separate the air inlets from the flue gas
outlets (excluding LENNOX supply).
SUPPLY NETWORK PIPE SIZING
MALE THREADED CONNECTION FOR GAS BURNER: 3/4”
,1” OR 1”1/4
Check that the gas supply line can provide the burners with the pressure and the gas flow rate necessary to provide the heating
nominal output.
WARNING: DO NOT FORGET TO CONNECT THE CONDENSATE DRAIN. THE CONDENSATES MUST ABSOLUTELY BE DRAINED
AT LEAST 5 METERS FROM THE UNIT INTO AN APPROPRIATE PLACE. THE CONDENSATES ARE CORROSIVE AND COULD
DAMAGE THE UNIT (OR OTHER PARTS OF THE INSTALLATION) IF THEY ARE NOT DRAINED PROPERLY.
CHIMNEY INSTALLATION
Depending site configuration / local regulation, an additional chimney could be install (not included with the unit). Please refer
to our Service & parts team.
CHIMNEY HORIZONTAL
CONNEXION