INSTALLATION
e-BALTIC-IOM-2020.12-EN
25
MINIMUM CLEARANCE AROUND THE UNIT
Figure below shows the required clearances and service access around the unit.
NOTE: Ensure the fresh air inlet does not face prevailing wind direction
•
Make sure that the fresh air duct is not in the same direction as the prevailing winds.
•
If machine is including gas burner, minimum clearance around the unit must be at least 8 m to allow a proper gas flue
dilution. If not possible, the fresh air intake must be ducted at least 8 m away from the gas burner exhaust.
•
In case of extraction option, it is recommended to duct fresh air intake.
•
An approach ramp must be installed if the unit’s installation requirements tell that it's necessary to reach the main switch,
the electrical cabinet, the compressor and the ventilation compartment. This recommendation is valid for all type of
installations.
•
It is also important to respect a minimal clearance of 3 meters above of the unit, to allow a good operation of the outdoor
fans.
A
B
C
D
E
Unit
(mm)
D BOX
1650 (1)
1000
1000
1000
3000
E BOX
2150 (1)
1000
1000
1000
3000
E+ BOX
2150 (1)
1000
1000
1000
3000
F BOX
2600 (1)
1000
1000
1000
3000
G BOX
2600 (1)
1000
1000
1000
3000
H BOX
2600 (1)
1000
1000
1000
3000
(1)
Add 1000 mm if the units are equipped with gas burner