HEAT RECOVERY
e-BALTIC-IOM-2020.12-EN
40
HEAT RECOVERY
GENERAL DESCRIPTION
Heat recovery modules (HRM) have following interests:
•
in winter season and heating mode, the heat in the extract air is exchanged with the fresh air ;
•
in summer season and cooling mode, the heat of the fresh air is transferred to the extract air.
HRM are two plates heat exchanger modules, that differ from each other by their horizontal (HRMH) or vertical (HRMV)
configuration.
TRMO is a thermodynamic heat recovery module, included in the machine. Its main interests are:
•
a variable fresh air rate from 25 to 100%,
•
a high COP in winter when pre-heating the fresh air due to a favorable evaporating temperature, especially with high air
flow rate;
•
a high EER in summer when pre-cooling the fresh air due to a favorable condensing temperature, especially with high air
flow rate.
For those reasons, TRMO will be more suitable than HRMV/HRMH in areas where the difference between indoor temperature
and outdoor temperature is low. For example, in Mediterranean areas, where winter temperatures are not very cold or
summer temperatures are not very high.
Содержание e-Baltic D BOX 55
Страница 51: ...HEAT RECOVERY e BALTIC IOM 2020 12 EN 48 STEP 3 FITTING STEP 4 CHECK 0 15 mm SAME LEVEL...
Страница 91: ......