Three-Sources Management System
(T.S.M.S.)
Installa
tion and user manual
5
1. Introduction
The Legrand 422684 control unit implements state-of-the-art functions reuired for control and managmrnt multisource.
The system incorporates a uniue series of hardware and software features which guarantee high flexibility, e.g.
management of three supply source lines and two tie breakers, graphic display, double power supply, expansion modules,
programmable system layout, integrated PLC etc., for use in a wide variety of possible conditions of application, all of
which can be programmed by the user.
The graphic display shows and allows to control the system situation effectively. The expansion slots allows to increase
the hardware resources also allowing adaptability to future needs.
1.1
Description
• Graphic LCD 128x112 pixel, backlit, 4 grey levels.
• Texts for measurements, settings and messages in 8 languages (ENG-ITA-FRA-SPA-DEU-POR-POL-RUS).
• 14 possible system configurations, with 2 or 3 power sources and 1 or 2 tie breakers.
• 3 voltage measuring inputs, three phase + neutral.
• Free source type configuration (mains or genset) and respective priority for all system configurations.
• Non-priority load management.
• Control of motorised breakers, motorised changeover switches or contactors.
• Management of gensets with automatic test and emergency rotation.
• Control of three phase, two-phase and single-phase networks.
• Control of concatenated voltages and/or phase voltages.
• Control of minimum voltage, maximum voltage, phase loss, asymmetry, minimum freuency, maximum freuency with
independent enabling and tripping delay.
• Voltage thresholds with programmable hysteresis.
• Possibility of transferring load with closed transition and spontaneous or controlled genset synchronisation.
• 100-240Vac auxiliary power supply.
• 12-24-48Vdc battery power supply.
• Front optical programming interface.
• Advanced programmable I/O functions.
• Integrated programmable PLC logic (50 lines, 8 columns).
• Alarm properties entirely definable by the user.
• High accuracy of true RMS measurements (TRMS)
• 12 programmable digital inputs (negative).
• 11 digital outputs:
- 3 relays with NO contact 12A 250VAC.
- 3 relays with NO contact 8A 250VAC.
- 4 relays with changeover contact 8A 250VAC.
- 1 static output.
• Integrated RS-485 isolated interface.
• 3 expansion slots modules.
• Storage of last 250 events.
• Real Time Clock.
• IP40 front protection expandable to IP65 by means of optional gasket.
• Compatible with softwer amd App Legrand ACU Legrand.