18
M02 - GENERAL
UNIT
DEFAULT
RANGE
P02.01
System layout
E 3S - 0T
E : 3S – 0T
F: 3S – 1T – PL
G: 3S – 1T – AI
H: 3S – 1T – PS
I: 3S -1T - RI
J: 3S – 1T - 12
K: 3S – 2T – M2
L: 3S – 2T - FL
M: 3S – 2T – 3N
N: 3S – 2T – 2L
O: (custom)
P02.02
Rated system voltage
V
400
50 – 50000
P02.03
VT Use
OFF
OFF-ON
P02.04
VT Primary
V
100
50-50000
P02.05
VT Secondary
V
100
50-500
P02.06
Phase seuence check
OFF
OFF
L1-L2-L3
L3-L2-L1
P02.07
Connection type
L1-L2-L3-N
L1-L2-L3-N
L1-L2-L3
L1-N-L2
L1-N
P02.08
Rated control type
L-L
L-L
L-N
L-L + L-N
P02.09
Rated freuency
Hz
50Hz
50 Hz
60 Hz
P02.10
CT position
OFF
OFF
LOAD
S1
S2
S3
P02.16
Non-priority load management
OFF
OFF
Pulse breaker
Continuous breaker
Contactor
P02.17
Breaker operation max. time non-priority load
sec
5
1…900
P02.18
Open pulse time
sec
10
0-600
P02.19
Close pulse time
sec
1
0-600
P02.20
Minimum coil opening pulse time
sec
1.0
0.1 … 10.0
P02.21
Delay between min. coils and spring load
sec
0.2
0.1 … 10.0
P02.22
Tie breaker management (QCCx)
OFF
OFF
Pulse breaker
Continuous breaker
Contactor
P02.23
Maximum tie breaker operation time
sec
5
1…900
P02.24
Open pulse time
sec
10
0-600
P02.25
Close pulse time
sec
1
0-600
P02.26
Minimum coil opening pulse time
sec
1.0
0.1 … 10.0
P02.27
Delay between min. coils and spring load
sec
0.2
0.1 … 10.0