Three-Sources Management System
(T.S.M.S.)
Installa
tion and user manual
21
M05 - ACOUSTIC ALARMS
UNIT
DEFAULT
RANGE
P05.01
Siren sound mode on alarm
Timed
OFF
Keypad
Timed
Repeated
P05.02
Sound activation time on alarm
sec
30
OFF/1-600
P05.03
Sound activation time before starting
sec
OFF
OFF / 1-60
P05.04
Sound activation time on remote control start
sec
OFF
OFF / 1-60
P05.05
Sound activation time for no line S.1
sec
OFF
OFF / 1-60
P05.06
Sound activation time for no line S.2
sec
OFF
OFF / 1-60
P05.07
Sound activation time for no line S.3
sec
OFF
OFF / 1-60
P05.08
Acoustic indication device
SIREN
OFF
SIREN
BUZZER
SIR
P05.09
Buzzer on key press
sec
0.15
OFF / 0.01-0.50
P05.01 - OFF = siren deactivated. Keypad = Siren sounds continuously until it is cancelled by pressing a button on the
front panel. Timed = Sounds for the time specified in P06.02. Repeated = Sounds for the time in P06.02, pause
for a triple time, and then repeats cyclically.
P05.02 - Acoustic signal activation time on alarm.
P05.03 - Acoustic signal activation time before any starting of the engine.
P05.04 - Acoustic signal activation time following activation of a remote control via communication channel.
P05.05 - P05.06 - P05.07 - Acoustic signal activation time following lack of power on S.1/2/3 line.
P05.08 - Acoustic signalling device choice.
P05.09 - Buzzer activation and time following button pressing.
M06 - SOURCE LINES
(Q.Sx, n=1…3)
UNIT
DEFAULT
RANGE
P06.n.01 Source description
.SQx
(char*6)
P06.n.02 Signal priority
n
1 – 3
P06.n.03 S.x source type
Mains
Mains
Genset
P06.n.04 Genset cooling time
sec
120
1-3600
P06.n.05
P06.n.06
P06.n.07
P06.n.08
P06.n.09
P06.n.10
P06.n.11
P06.n.12
P06.n.13
Note: This menu is divided into 3 sections for source lines S.Q1 S.Q2 S.Q3.
P06.n.01 - Alphanumeric description on the respective power source line which will be shown on the display synoptic panel.
P06.n.02 - Power line priority. In case of simultaneous presence of multiple power lines on the same load, the one with
priority 1 is connected. If the line with priority 1 is not present, the one with priority 2 is used etc. If two sources
are programmed with the same priority, the software attribute higher priority to the one most on the left.
P06.n.03 - This defines the type of power source of the S.x line. Mains = The mains symbols is shown on the synoptic
panel. Genset = The genset symbol is shown and the start/stop outputs are managed; is sought.