38
NR.
FUNCTION
DESCRIPTION
67
Q.C1 tie breaker protection trip
As above, referred to Q.C1.
68
Q.C2 tie breaker protection trip
As above, referred to Q.C2.
69
NPL breaker withdrawn
The input generates NPL breaker withdrawn alarm when the contact
opens.
70
Q.C1 tie breaker withdrawn
As above, referred to Q.C1.
71
Q.C2 tie breaker withdrawn
As above, referred to Q.C2.
72
Close Q.C1
When in MAN mode, commands Q.C1 closing.
73
Open Q.C1
When in MAN mode, commands Q.C1 opening.
74
Toggle Q.C1
When in MAN mode, commands Q.C1 toggle.
75
Close Q.C2
When in MAN mode, commands Q.C2 closing.
76
Open Q.C2
When in MAN mode, commands Q.C2 opening.
77
Toggle Q.C2
When in MAN mode, commands Q.C2 toggle.
2.25
Programmable input default
INPUT
TERMINALS
DEFAULT FUNCTION
INP1
40
Breaker Q1 closed (Feedback 1)
INP2
41
Breaker Q2 closed (Feedback 2)
INP3
42
Breaker Q3 closed (Feedback 3)
INP4
43
Breaker Q1 closed (Trip 1)
INP5
44
Breaker Q2 closed (Trip 2)
INP6
45
Breaker Q3 closed (Trip 3)
INP7
46
Priority genset start (Off load)
INP8
47
Transfer to secondary load (remote start on-load)
INP9
49
Automatic return to priority line inhibition
INP10
50
Disabled
INP11
51
Disabled
INP12
52
Disabled
2. Operating modes