Three-Sources Management System
(T.S.M.S.)
Installa
tion and user manual
41
2.27
Programmable outputs default
OUTPUT
TERMINALS
DEFAULT FUNCTION
OUT1
55-56
Open breaker Line 1 Q1)
OUT2
56-57
Close contactor/breaker line 1 (Q1)
OUT3
58-59
Open breaker Line 2 (Q2)
OUT4
59-60
Close contactor/breaker line 2 (Q2)
OUT5
61-62
Open breaker Line 3 (Q3)
OUT6
62-63
Close contactor/breaker line 3 (Q3)
OUT7
19-20-21
Global alarm A
OUT8
28-29
ATS Ready
OUT9
30-31-32
Control genset 1
OUT10
33-34-35
Control genset 2
OUT11
36-37-38
Control genset 3
2.28
System layout
The possible system layouts supported by the ref. 422684 are listed below. The following information is provided for
each one:
• The code used for selecting the layout type in the parameter setting P02.01 of the GENERAL menu (example: B: 2S-1T-PL)
• An example of synoptic
• A truth table
• A description of a typical application.
Codes are used by way of examples in these synoptic to identify the single elements. Note that the text of these codes
can be freely programmed to make them correspond to the real system. In our examples, the code indicate the following:
• Q.Sx = SOURCE power line Corresponding to the Q.Sx power lines.
• Qx = Line breaker. Corresponding to the Qn breakers.
• TBx = Tie Breaker.
• LOADx = User load.
• NPL = Non-Priority Load.
2.29
Command menu
• The
Command menu
is used to perform occasional operations, like resetting measurements, counters, alarms etc.
• If the advanced access password was entered, the command menu can also be used to perform automatic operations
useful for configuring the instrument.
• The following table shows the functions which are available with the command menu divided according to the required
access level.
CODE
CONTROL
ACCESS LEVEL
DESCRIPTION
C01
RESET MANTENACE HOURS 1
ADVANCED
Reset maintenance interval hours of the breaker 1
C02
RESET MANTENACE HOURS 2
ADVANCED
Reset maintenance interval hours of the breaker 2
C03
RESET MANTENACE HOURS 3
ADVANCED
Reset maintenance interval hours of the breaker 3
C04
RESET MANTENACE COUNTER 1
ADVANCED
Reset maintenance interval operations of the breaker 1
C05
RESET MANTENACE COUNTER 2
ADVANCED
Reset maintenance interval operations of the breaker 2
C06
RESET MANTENACE COUNTER 3
ADVANCED
Reset maintenance interval operations of the breaker 3
C07
RESET GENERIC
COUNTERS CNTX
USER
Resets generic counters CNTx
C08
RESET LIMX
USER
Reset limits LIMx variable status
C09
RESET HOURS SOURCE 1
ADVANCED
Reset hours counter of load supplied by source 1
continue