M15 - LIMIT THRESHOLDS
(LIMn, n = 1…16)
UNIT
DEFAULT
RANGE
P15.n.01
Reference measurement
OFF
OFF-
(measurements list)
AINx
CNTx
….
P15.n.02
Reference measurement source
OFF
OFF
S.1
S.2
S.3
P15.n.03
Channel no. (x)
1
OFF/1..99
P15.n.04
Function
Max
Max
Min
Min+Max
P15.n.05
Upper threshold
0
-9999 - +9999
P15.n.06
Multiplier
x1
/100 - x10k
P15.n.07
Delay
sec
0
0.0 – 600.0
P15.n.08
Lower threshold
0
-9999 - +9999
P15.n.09
Multiplier
x1
/100 - x10k
P15.n.10
Delay
sec
0
0.0 – 600.0
P15.n.11
Home state
OFF
OFF-ON
P15.n.12
Memory
OFF
OFF-ON
Note: This menu is divided into 16 sections for limit thresholds LIM1..16.
P15.n.01 - This defines which measurements supplied by the ref. 422684 to apply the limit threshold.
P15.n.02 - If the reference measurement is an electric measurement, this defines whether it refers to the mains or the
genset.
P15.n.03 - If the reference measurement is a multichannel internal measurement (e.g. AINx), this defines which channel.
P15.n.04 - This defines the limit threshold operating mode. Max = LIMn active when the measurement is higher than
P15.n.03. P15.n.06 is the resetting threshold. Max = LIMn active when the measurement is lower than P15.n.06.
P15.n.03 is the resetting threshold. Min+Max = LIMn active when the measurement is higher than P15.n.03
or lower than P15.n.06.
P15.n.05 and P15.n.06 - These define the upper threshold which is given by the value of P15.n.03 multiplied by P15.n.04.
P15.n.07 - Tripping delay on the upper threshold.
P15.n.08, P08.n.09, P08.n.10 - as above referred to the lower threshold.
P15.n.11 - This allows to reverse the LIMn limit state.
P15.n.12 - This defines whether the threshold remains stored or must be manually reset using the command menu (ON)
or whether it resets automatically (OFF).