Three-Sources Management System
(T.S.M.S.)
Installa
tion and user manual
31
M17 - TIMER
(TIMn, n = 1…8)
UNIT
DEFAULT
RANGE
P17.n.01
Timer source
OFF
ON
INPx
OUTx
LIMx
REMx
PLCx
Axx
UAx
RALx
P17.n.02
Channel no. (x)
1
1-99
P17.n.03
Delay
sec
0
0.0 – 6000.0
Note: This menu is divided into 8 sections for the timers TIM1..8.
P17.n.01 - Source variable which controls the starting and resetting of the concerned timer.
P17.n.02 - Channel number referred to the previous parameter.
P17.n.03 - Timer time.
M18 – REMOTE ALARMS
(RALn, n = 1…24)
UNIT
DEFAULT
RANGE
P18.n.01
RALn output function
(miscellaneous)
(see Output functions
table )
P18.n.02
Function index (x)
OFF
OFF / 1…99
P18.n.03
Normal/reverse output
NOR
NOR / REV
Note: this menu is divided into 24 sections for state/alarm remoting variables RAL1…RAL24, available in
combination with the external unit RGKRR
P18.n.01 - This selects the remote output function RALn. The remote outputs (remote unit relay RGKRR) may assume the
same functions as the local outputs, including the operating states, the alarms etc.
P18.n.02 - Index possibly associated to the function programmed under the previous parameter. Example: If the function
of the output is set to the Alarm Axx function and this output must be energised when alarm A31 occurs, then
P18.n.02 is set to value 31.
P18.n.03 - This sets the output state when the associated function is not active: NOR = de-energised output, REV =
energised output.
M21 - USER ALARMS
(UAn, n=1…8)
UNIT
DEFAULT
RANGE
P21.n.01
Alarm source
OFF
OFF
INPx
OUTx
LIMx
REMx
PLCx
TIMx
P21.n.02
Channel no. (x)
1
OFF/1...99
P21.n.03
Text
UAn
(text - 20 characters)
P21.n.04
Breaker 1 open
OFF
OFF
ON
P21.n.05
Breaker 2 open
OFF
OFF
ON
P21.n.06
Breaker 3 open
OFF
OFF
ON