Three-Sources Management System
(T.S.M.S.)
Installa
tion and user manual
39
2.26
Programmable outputs functions table
• The following table shows all the functions which can be associated to the programmable digital outputs OUTn.
• Each output may be controlled in normal or inverted function (NOR or REV).
• Other functions reuire a further numeric parameter defined by index (x) specified by parameter P13.n.02.
• See menu
M13 Programmable outputs
for more details.
NR.
FUNCTION
DESCRIPTION
0
Disabled
Output disabled.
1
Configurable
Freely configurable by the user.
2
Close contactor/breaker line 1 Closing control of relay/switch / Line 1 (Q1).
3
Open breaker Line 1
Opening control of breaker Line 1 (Q1) and possible spring loading.
4
Close contactor/breaker line 2
Closing control of relay/switch / Line 2 (Q2).
5
Open breaker Line 2
Opening control of breaker Line 2 (Q2) and possible spring loading.
6
Close contactor/breaker line 3
Closing control of relay/switch / Line 3 (Q3).
7
Open breaker Line 3
Opening control of breaker Line 3 (Q3) and possible spring loading.
8
Open Q1/2/3
Opening of both breakers/neutral position motorised transfer.
9
Minimum coil Q1 (UVR )
Controls the minimum voltage coil by opening breaker Q1 before the
spring loading cycle.
10
Minimum coil Q2 (UVR )
As above, referred to Q2.
11
Minimum coil Q3 ( UVR)
As above, referred to Q3.
12
Control genset 1
Control remote start/stop of genset on line S.Q1.
13
Control genset 2
As above, referred to S.Q2.
14
Control genset 3
As above, referred to S.Q3.
15
ATS ready
ATS in automatic, without alarms, ready to transfer.
16
Global alarm A
Output activated in presence of any alarm with
Global alarm
A property activated.
17
Global alarm B
Output activated in presence of any alarm with
Global alarm
B property activated.
18
Voltage state line S.Q1
Output energised when all consitions exit to connect the load to the
Q.S1 line.
19
Voltage state line S.Q2
As above, referred to S.Q2.
20
Voltage state line S.Q3
As above, referred to S.Q3.
21
Siren
Powers the acoustic warning siren.
22
Operative mode
Output energised when the ref. 422684 is in one of the modes set
with parameter P14.03.
23
OFF mode
Energised when ref. 422684 is in OFF mode.
24
MAN mode
Energised when ref. 422684 is in MANUAL mode.
25
AUT mode
Energised when ref. 422684 is in AUT mode.
26
TEST mode
Energised when ref. 422684 is in TEST mode.
27
REM(x) remote variable
Output controlled by remote variable REMx (x=1..16).
28
LIM (x) limits
Output controlled by limit threshold state LIM(x) (x=1..16) defined by the
index parameter.
29
Dummy load Line S.Q1
Output enabled when the automatic test is performed with dummy
load line SQ1.
30
Dummy load Line S.Q2
As above, referred to line SQ2.
31
Dummy load Line S.Q3
As above, referred to line SQ3.
32
Load on Line S.Q1
Breaker Q1 closed.
continue