Three-Sources Management System
(T.S.M.S.)
Installa
tion and user manual
37
NR.
FUNCTION
DESCRIPTION
31
Keypad lock
If closed, locks all front keyboard functions except for measurement display.
32
Parameter setting lock
If closed, the setup menu access is locked.
33
Remote control lock
Locks control and writing operations via serial port.
Data reading is always possible.
34
Siren OFF
Deactivates the siren.
35
Automatic test
Starts a periodical test managed by an external timer.
41
Reset alarms
Reset retraining alarms the causing condition of which has ceased.
42
Control menu C(xx)
Executes the command menu control defined by the index parameter
(xx).
43
Simulate OFF button
Closing the input is equivalent to pressing the button.
44
Simulate MAN button
Closing the input is equivalent to pressing the button.
45
Simulate AUT button
Closing the input is equivalent to pressing the button.
46
Simulate TEST button
Closing the input is equivalent to pressing the button.
47
Automatic test inhibition
Prevents automatic test execution.
48
LED test
Lights up all LEDs on the front panel making them blink.
49
Close Q1
Closes breaker Q1 in manual mode.
50
Open Q1
Opens breaker Q1 in manual mode.
51
Toggle Q1
Toggles the state of breaker Q1 in manual mode.
52
Close Q2
Closes breaker Q2 in manual mode.
53
Open Q2
Opens breaker Q2 in manual mode.
54
Toggle Q2
Toggles the state of breaker Q2 in manual mode.
55
Close Q3
Closes breaker Q3 in manual mode.
56
Open Q3
Opens breaker Q3 in manual mode.
57
Toggle Q3
Toggles the state of breaker Q3 in manual mode.
58
Auxiliary voltage ready
NC contact which, if opened, generates alarm
A30 Auxiliary voltage
breaker alarm
. Used in combination with the DPS REF . 422686 DUAL
POWER SUPLLY alarm relay.
59
Service mode
If enable for system Service, this causes:
• Deactivation of feedback timeout alarms A03 A04 A05
• Switching to OFF mode
• Energising of minimum voltage coils.
60
Non-priority load breaker
feedback
Auxiliary contact which informs the ref. 422684 of the open/closed
state of breaker which breaks the non-priority load. If this signal
is not connected, ref. 422684 considers the state of the breaker
corresponding to the control output state.
61
Maximum priority line S.Q1
When closed, line SQ1 becomes the priority line.
62
Maximum priority line S.Q2
As above, referred to line S.Q2.
63
Maximum priority line S.Q3
As above, referred to line S.Q3.
64
Tie breaker QC1 feedback
Auxiliary contact which informs the ref. 422684 of the open/closed
state of tie breaker QC1. If this signal is not connected, ref. 422684
considers the state of the tie breaker corresponding to the control
output state.
65
Tie breaker Q.C2 feedback
As above, referred to Q.C2.
66
NPL breaker protection trip
The input generates NPL breaker protection tripping
when the contact closes.
continue