Palletizing Solution - Instruction Manual
Wire #
Color
Function
Description
1
White
Safety-Reset
l
When using area scanner: Connect wire #1 to available 24V in UR controller. The system will
auto-start when you step out of the protected area.
l
When using light curtain: Connect wire #1 to normally-open (NO) reset switch. Connect switch's
second pole to available 24V in UR controller. Place reset switch outside of the protected area.
2
Brown
0V
0V link between both electrical enclosures.
3
Green
UR E-Stop Status 1
E-Stop status signal when a emergency signal is applied to EI0.
4
Yellow
UR E-Stop Status 2
E-Stop status signal when a emergency signal is applied to EI1.
5
Grey
UR Safeguard input 1
UR does not support a safeguard status in configurable outputs. Connect this pin to the regular
safeguard input SI0 for status.
6
Orange
UR Safeguard input 2
UR does not support a safeguard status in configurable outputs. Connect this pin to the regular
safeguard input SI1 for status.
Table 12-1: Safety Wires Description
Содержание ROBOTIQ AX Series
Страница 4: ...Palletizing Solution Instruction Manual 4...
Страница 14: ...Palletizing Solution Instruction Manual 14...
Страница 21: ...Palletizing Solution Instruction Manual 21...
Страница 82: ...6 1 2 AirPick Vacuum Gripper Fig 6 1 AirPick general dimensions 82...
Страница 83: ...Palletizing Solution Instruction Manual 6 1 3 Extra Reach Bracket 83...
Страница 84: ...6 1 4 Bracket for Two 2 Suction Cups Fig 6 2 Two air nodes bracket s dimensions 84...
Страница 110: ...1 2 2 Safety Connections Fig 12 2 Universal Robots Controller Safety Connections Schema 110...