![Lake Shore 648 Скачать руководство пользователя страница 25](http://html1.mh-extra.com/html/lake-shore/648/648_user-manual_670640025.webp)
2.5.3 Operation Under Field Control
15
|
www.lakeshore.com
2.5.3 Operation Under
Field Control
To obtain a linear field ramp, a magnetic sensor such as a Hall probe is placed in the
air gap along with the sample being tested. The sensor is connected to a gaussmeter.
The output of the gaussmeter is used to correct the programming input to the power
supply. In this way non-linearity can be corrected. Lakeshore manufactures probes
and gaussmeters for this purpose.
2.5.4 Avoiding Cooling
Water Condensation
If the temperature of the cooling water is too cool relative to the air temperature and
humidity, condensation can occur. Condensation inside the power supply can cause
severe damage. To avoid condensation, the power supply operator must remain
cognizant of the ambient air temperature, cooling water temperature, and the
relative humidity. Lake Shore defines the limits of these conditions as follows:
D
ambient temperature = 18 - 28 °C (64 - 82 °F)
D
cooling water temperature = 15 - 25 °C (59 - 77 °F)
D
humidity = 20 - 80% (non-condensing).
Knowing the actual state of these conditions, the operator can calculate the dew
point, or temperature at which condensation will occur. TABLE 2-1 and TABLE 2-2 are
included to aid in dew point calculation.
Dew point calculation (in degrees Celsius)
% Relative Humidity
°C
100
95
90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10
32
32
31
31
29
28
27
26
24
23
22
20
18
17
15
12
9
6
2
0
29
29
28
27
27
26
24
23
22
21
19
18
16
14
12
10
7
3
0
—
27
27
26
25
24
23
22
21
19
18
17
15
13
12
10
7
4
2
0
—
24
24
23
22
21
20
19
18
17
16
14
13
11
9
7
5
2
0
—
—
21
21
20
19
18
17
16
15
14
13
12
10
8
7
4
3
0
—
—
—
18
18
17
17
16
15
14
13
12
10
9
7
6
4
2
0
—
—
—
—
16
16
14
14
13
12
11
10
9
7
6
5
3
2
0
—
—
—
—
—
Dew point calculation (in degrees Fahrenheit)
% Relative Humidity
°F
100
95
90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10
90
90
88
87
85
83
81
79
76
74
71
68
65
52
59
54
49
43
36
32
85
85
83
81
80
78
76
74
72
69
67
64
61
58
54
50
45
38
32
—
80
80
78
77
75
73
71
69
67
65
62
59
56
53
50
45
40
35
32
—
75
75
73
72
70
68
66
64
62
60
58
55
52
49
45
41
36
32
—
—
70
70
68
67
65
63
61
59
57
55
53
50
47
44
40
37
32
—
—
—
65
65
63
62
60
59
57
55
53
50
48
45
42
40
36
32
—
—
—
—
60
60
58
57
55
53
52
50
48
45
43
41
38
35
32
—
—
—
—
—
Example: Determine the actual air temperature and relative humidity. Find the
closest air temperature in the left-hand column and the closest relative humidity
across the top. If the air temperature is 24 °C (75 °F) and the relative humidity is 35%,
the intersection of the two shows a dew point of 7 °C (45 °F). Therefore, for the given
conditions, the cooling water must remain above 7 °C (45 °F) to prevent
condensation.
TABLE 2-1
TABLE 2-2