KW Aufzugstechnik GmbH Inbetriebnahme DAVID-613
DAVID-D613-Inbetriebnahme-V124-EE 18.02.2022 Seite - 72 -
4.0 STEP-3: Safekopierung – teach zones
Navigate with arrow keys and select the menu
item with ENTER.
Navigate with yellow keys and enter "yes"
Note: Elevator moves 2x all floors. Afterwards, the
status of the ANTS safe system is in "normal
mode" and all zones are output and monitored
4.1 Adjustment of releveling
Before you activate readjustment, you must make the following parameter set-
tings in menu B17 readjustment:
7.1
In parameter
Max. Catch-up distance
you set the length of the catch-up path. The distance
should always be shorter than half the zone area. Please also note the following facts: The
zone area must be set so that it is shorter than the length of the door.
7.2
In parameter
Tolerance Recall
you set the starting point for the start of the retrieval.
By
default, you should not go below 5 - 10mm
, as otherwise existing rope vibrations lead to
unnecessary readjustment.
If the above entries have been made, the parameter
Recall
can be activated.
4.2 ANTS- SAFE – copy – error handling
If the ANTSsafe detects a serious fault and locks itself, this condition can only be reset for safety rea-
sons by deactivating the power supply and switching on the 24VDC on the ANTSsafe again.
This can be done on the D613 by briefly changing the state of the inspection or return switch. This will
set the output function A611 for 2 sec. The function A611 should control a relay, which will break the
24V supply voltage at the ANTSsafe
.