KW Aufzugstechnik GmbH Inbetriebnahme DAVID-613
DAVID-D613-Inbetriebnahme-V124-EE 18.02.2022 Seite - 17 -
34
Installation of the SGS92 shaft pit
Attention!
The pit may only be entered if it is longer than 15 minutes if the
car is fixed with a support!
The shaft pit is to be installed at a height of 2.0 m. The grip area should be
approx. 0.75m!
35
Connection of the shaft pit SGS92
The shaft pit station contains two modules,
namely the ERG-2018 floor computer pit (left)
and the X6 module (right).
On the X6 assembly, the X6 cable is already
plugged in. In the control unit, the pre-assembled
connectors are connected to the positions:
X1/3, X1/4 & X1/5
to the left of the suspension cable.
In addition, the bus cable gray is plugged into the
BIS-80 on the far right!
Attention! The cables may only be connected
in a de-energized state!
On the left you can see the connection di-
agram, which is also located in the cover
of the shaft pit.
In it you can see the function and the ter-
minal of your switch.
If you have locked yourself in the shaft pit
(control is on error!), there is the possibility
via the reset button and the procedure with
the inspection control pit of the self-clear-
ing.
Attention! The lines may only be connected
in a de-energized state!
Non-existing safety circuit switches are
bridged in the terminals.
36
Connection of the shaft lighting socket strip SDL-92 in
the pit box
Attention! The connection of the socket strip for the shaft lighting may only be carried
out in a de-energized state! Fuse F4 -> OFF! The terminal for connecting the shaft light-
ing can be found on the ERG-2018 circuit board (circuit diagram sheet 3 of 8).
Shaft lighting
Phase 230V AC
L42
Earth
PE
Neutral conductor
N4
37
Connection of the LED shaft lighting
The socket strip is mounted as shown in the picture with the strip hang-
ing down.
Up to 4 shaft lighting strings can be connected. Plugs & cables are
strain relieved with cable ties. Please close unused sockets with the
cap.