KW Aufzugstechnik GmbH Inbetriebnahme DAVID-613
DAVID-D613-Inbetriebnahme-V124-EE 18.02.2022 Seite - 46 -
90
Connection of the door drives via CANOpen
This is plugged into the lower CANbus terminal on the X11-XPU
module in the de-energised state.
Further door drives are extended with further CANbus cables on the
preceding line.
The last device is provided with a terminating resistor.
The connection of the door motor must only be carried out in a voltage-free state
! (Cir-
cuit diagram sheet 2 of 8).
The reversing contactor unit is located in an additional box
613. There is also space for the locking magnet control and an optional transformer.
Phase U Door-Engine Door 1
UA
Phase V Door-Engine Door 1
VA
Phase W Door-Engine Door 1
WA
Phase U Door-Engine Door 2
UB
Phase V Door-Engine Door 2
VB
Phase W Door-Engine Door 2
WB
92
Connection of the Photocell Door-1, Door-2 & Door-3
Attention! All inputs are + 24V DC inputs! Avoid the application of external voltage at
these terminals! The terminal for the connection of the light grating can be found on the
circuit board X11/.
+ 24V Voltage
200
+ 24V or 0V DC Input Photocell DOOR 1 / 2 / 3
42A/B/C
+ 24V DC Input Error Photocell DOOR 1 / 2 / 3
48A/B/C
0V GND
500
Set to PNP or NPN light curtains by means of the Jumper Right Top
93
Connection of the Audiovisual Alert H69
Attention! All inputs are + 24V DC inputs! Avoid the application of external voltage at
these terminals! The terminal for the connection of the light grating can be found on
the
circuit board X11 /.
The terminals are
169 and 500.
94
Connection of the Door-End-Switch, Revers-Con-
tact
Attention! All inputs are + 24V DC inputs! Avoid the application of external volt-
age at these terminals!
Attention! Inputs can be unlocked! Be sure to observe page 2 of 8 in the set!
Default setting:
Input Revers-Contact DOOR 1
FF1
Input Door-End-Switch-OPEN DOOR 1
FF2
Input Door-End-Switch-CLOSE DOOR 1
FF3
Input Revers-Contact DOOR 2
FF5
Input Door-End-Switch-OPEN DOOR 2
FF6
Input Door-End-Switch-CLOSE DOOR 2
FF7
95
Connection of the transom mate
The latching solenoid may only be connected in a de-energised state!
(Circuit diagram sheet 2 of). The connection is located in the additional box-613
Phase AC or + Voltage DC
715
N or 0V
716
Ground
PE