KW Aufzugstechnik GmbH Inbetriebnahme DAVID-613
DAVID-D613-Inbetriebnahme-V124-EE 18.02.2022 Seite - 44 -
78
Connection of the Emergency-Stop-Switch Cabin
ONLY WITH HYDRAULICS INDIRECT 2:1
Attention! The connection of the safety circuit contacts may only be carried out in
the de-energized state!
The terminal for connecting the auxiliary emergency stop switch for a second
Emergency stop switch on the cabin can be found on the circuit board X11 /,
(Wiring diagram sheet 4 of 8 / column 4).
The terminals are
3D and 3E.
If not present, please contact bridge!
79
Connection of the Inspection-End-Switch
ONLY WITH HYDRAULICS INDIRECT 2:1
Attention! The connection of the safety circuit contacts may only be carried out in the de-
energized state!
The terminal for the connection of the emergency end switch with shortened shaft
head can be found on the printed circuit board X11
/,
(Wiring diagram sheet 4 of 8 / column 4).
The terminals are 4D and 4E.
If not present, please contact bridge!
80
Connection of the Folder-Railing-Switch - 1
Attention! The connection of the safety circuit contacts may only be carried out in the de-
energized state!
The terminals for connecting the Folder-Railing-Switch - 1 with shortened shaft head can
be found on the circuit board X11 /, (
wiring diagram sheet 4 of 8 / column 5-6).
The terminals are
3F and 3G, as well as 4F and 4G.
If not present, please provide contacts with bridges!
81
Connection of the Folder-Railing-Switch - 2
Attention! The connection of the safety circuit contacts may only be carried out in the de-
energized state!
The terminals for connecting the Folder-Railing-Switch - 2 with shortened shaft head can
be found on the circuit board X11 /, (
wiring diagram sheet 4 of 8 / column 5-6).
The terminals are
3G and 3H, as well as 4G and 4H.
If not present, please provide contacts with bridges!
82
Connection of the message folding railing NO contact
+24V
Attention! The connection may only be made in a de-energised state!
The terminals for connecting the folding guard-rail switch - make contact 24V for actuat-
ing the protective space lights can be found on
the circuit board X11-XPU, (circuit dia-
gram sheet 5 of 8 / column 7-8).
The terminals are
6F and 6G.
83
Assembly of the safety room head H22 at RSH
Attention! The installation of the shelter lamp is done in the arrangement that the view of
the traffic light when opening the landing door is guaranteed. For a through-loading at the
stop, two protective clearance lights are to be installed.
Attention! The connection may only be made in a de-energised state!
The terminals for the connection of the protective space light head with shortened shaft
head can be found on the
circuit board X11-XPU, (circuit diagram sheet 5 of 8 / col-
umn 6-8).
The terminals are
RED -500-GREEN