1.
Check if the Control Transformer button is pulled
out.
4.
Is there 110 VAC between #1 & #2 on the 110 VAC Terminal Strip? If not, check
the fuse on the output side of the Control Transformer. If fuse is good, check power
coming out of Control Transformer.
5.
If no power on the output side, and there is power going into the top of the Control
Transformer, replace the Control Transformer.
6.
If there is power at the Control Transformer, check the wiring of the black and
white wire going from the Control Transformer to the 110 VAC Terminal Strip.
2.
Is the Disconnect Switch on the main electrical cabinet set to
ON?
Switch
3.
Is there 208, 220, 440, or 575 VAC to the top side (input) of the Control Trans-
former? If not, check the fuses at the Fuse Block, and the contacts on the Control
Transformer button on the switch panel.
Input
High Vac
Output
110 Vac
Typical Control Transformer
Control Power Light OFF
Troubleshooting Electrical Problems
6-27
KVAL Operation/Service Manual
Содержание Edge-SS
Страница 5: ...KVAL Edge SS Operation Service Manual ...
Страница 12: ...KVAL Edge SS Line Operation Service Manual ...
Страница 30: ...How to Download the Service Application 1 18 KVAL Operation Service Manual Page Intentionally Left Blank ...
Страница 32: ...Safety Sign Off Sheet 1 20 KVAL Operation Service Manual ...
Страница 35: ...Definitions 2 45 KVAL Operation Service Manual ...
Страница 91: ...Definitions KVAL Operation Service Manual 2 56 ...
Страница 109: ...System IT Administration 4 4 KVAL Operation Service Manual ...
Страница 142: ...Collet Torque Values 5 33 KVAL Operation Service Manual ...
Страница 143: ...Troubleshooting Electrical Problems 6 30 KVAL Operation Service Manual ...
Страница 173: ......
Страница 177: ......
Страница 178: ......
Страница 179: ......