STATus Command
KIKUSUI Electronics Corp.
PWR-01 Interface Manual
STAT:QUES:INST:PTR
Sets the positive transition of the QUEStionable:INSTrument subregister.
Command
STATus:QUEStionable:INSTrument:PTRansition <NRf>
STATus:QUEStionable:INSTrument:PTRansition?
Parameter
Value:0 to 2147483647
Response
Returns the positive transition of the QUEStionable:INSTrument subregister in NR1
format.
QUEStionable:INSTrument:ISUMmary<n> subregister
This is the subregister of bit <n> of the QUEStionable:INSTrument subregister. This
is a 16-bit register that stores information related to the status of and the question-
able events that occur during operation of the PWR-01 whose channel you speci-
fied.
Use <n> to specify the channel number.
For example, channel 2 is specified as "QUES:INST:ISUM2".
The QUEStionable status register bits may indicate that there are problems with
the PWR-01's measured data.
Bit Bit
weight
Bit name
Description
0
1
OVP (OV)
Overvoltage protection has been activated
1
2
OCP (OC)
Overcurrent protection has been activated
2
4
AC (PF)
Low AC input protection has been activated
3
8
Front Panel OCP (FOCP)
Front panel overcurrent protection has been acti-
vated
4
16
Over Temperature Protection
(OT)
Overheat protection has been activated
5
32
Shut Down protection (SD) Shut down
6
64
PARAllel protection (PARA) Incorrect parallel operation connection has been
activated
7
128
SENSing protection (SENS) Incorrect sensing connection protection has been
activated
8
256
NOT USED
--
9
512
NOT USED
--
10 1024 NOT USED
--
11 2048 Internal commuication failure
(12C)
--
12 4096 NOT USED
--
13 8192 NOT USED
--
14 16384 WatchDOG protection
(WDOG)
Communication monitor has been activated
15 32768 NOT USED
Always zero