Note that the minimum wire size required to prevent overheating may not be large enough to prevent
over-voltage tripping or maintain good regulation. Under most conditions, the load wires should also
be heavy enough to limit the voltage drop to no more than l.0 V per lead.
To help prevent nuisance tripping of the over-voltage circuit, select a wire size sufficient to handle the
FULL output current of the unit no matter what the intended load current or current limit setting.
Load lead resistance is also an important factor relating to the CV stability of the instrument when
remote sensing capacitive loads. If high capacitance loads are expected, you should not use wire
gauges heavier than 12 to 14 AWG for long runs of load lead.
Wire Size
Metric size (Note1)
Resistance
Max length to limit voltage to 1 V/lead
for 5 A
for 10 A
for 20 A
for 50 A
AWG
2 wires
bundled
4 wires
bundled
Ω
per foot
Wire length in feext
20
7.8
6.9
0.0102
20
x
x
x
18
14.5
12.8
0.0064
30
15
x
x
16
18.2
16.1
0.0040
50
25
x
x
14
29.3
25.9
0.0025
80
40
20
x
12
37.6
33.2
0.0016
125
63
30
x
10
51.7
45.7
0.0010
200
100
50
20
8
70.5
62.3
0.0006
320
160
80
32
6
94
83
0.0004
504
252
126
50
Area in mm2
2 wires
bundled
4 wires
bundled
Ω
per meter
Wire length in meters
0.5
7.8
6.9
0.0401
5
x
x
x
0.75
9.4
8.3
0.0267
7.4
x
x
x
1
12.7
11.2
0.0200
10
5
x
x
1.5
15.0
13.3
0.0137
14.6
7.2
x
x
2.5
23.5
20.8
0.0082
24.4
12.2
6.1
x
4
30.1
26.6
0.0051
39.2
19.6
9.8
3.9
6
37.6
33.2
0.0034
58
29
14.7
5.9
10
59.2
52.3
0.0020
102
51
25
10.3
Notes:
1. Capacity for AWG wires from MIL-W-5088B. Maximum ambient temperature: 55°C. Maximum wire temperature: 105°C
2. Capacity for metric wires from IE Publication 335-1.
3. Capacity of aluminum wire is approximately 84% of that listed for copper wire.
4. “x” indicates wire is not rated for the maximum output current of the power module.
5. Because of wire inductance considerations, it is also recommended that you keep your load leads twisted, tie wrapped, or
bundled together and less than 50 feet (14.7 meters) in length per lead.
Keysight N6705C Operating and Service Guide
57
2 Installation
Содержание N6705C
Страница 76: ......
Страница 353: ...Status Diagram Keysight N6705C Operating and Service Guide 353 7 SCPI Programming Reference ...
Страница 376: ...8 Verification and Calibration 376 Keysight N6705C Operating and Service Guide ...
Страница 389: ...Keysight N6705C Operating and Service Guide 389 8 Verification and Calibration ...
Страница 434: ......
Страница 438: ...9 Service and Maintenance 438 Keysight N6705C Operating and Service Guide ...
Страница 459: ...Overall Troubleshooting Keysight N6705C Operating and Service Guide 459 9 Service and Maintenance ...
Страница 460: ...9 Service and Maintenance 460 Keysight N6705C Operating and Service Guide ...
Страница 461: ...Keysight N6705C Operating and Service Guide 461 9 Service and Maintenance ...
Страница 462: ...9 Service and Maintenance 462 Keysight N6705C Operating and Service Guide ...
Страница 463: ...Keysight N6705C Operating and Service Guide 463 9 Service and Maintenance ...
Страница 470: ...Mezzanine Parts 9 Service and Maintenance 470 Keysight N6705C Operating and Service Guide ...
Страница 471: ...Front Panel Parts Keysight N6705C Operating and Service Guide 471 9 Service and Maintenance ...
Страница 476: ......