Keyboard Operation
16
4.2 The Customer Specified Parameter Group ( cP )
The cP parameter group is defined in the ud-group (USER DEFINTION) and
can’t
be
changed.
UP/DOWN is used to change between these parameters. A change of the group or set
is not possible. FUNCT is used to switch between the parameter value display and
parameter identification.
To change from the standard parameter group to the customer group and vice versa
the corresponding passwords must be entered (see chapter 5.7 / parameter ud. 0).
Display Application
Parameter
Parameter
Adjust. range
Resolution
Factory
setting
CP. 0
ud.0
Password input
0…9999
1
_
CP. 1
ru.3
Actual speed display
_
0.0125 Hz
_
CP. 2
ru.0
Inverter status
_
1
_
CP. 3
ru.7
Apparent current
_
1 %
_
CP. 4
ru.8
Peak apparent current
_
1 %
_
CP. 5
uF.0
Actual torque
0..409.58 Hz
0.0125 Hz
50.0 Hz
CP. 6
uF.1
Boost
0...25.5 %
0.1 %
2.0 %
CP. 7
oP.11
Acceleration time
0.01…300 s
0.01 s
10 s
CP. 8
oP.12
Deceleration time
0.01…300 s
0.01 s
10 s
CP. 9
oP.4
Minimum Reference
0…409.58 Hz
0.0125 Hz
0 Hz
CP. 10
oP.5
Maximum Reference
0…409.58 Hz
0.0125 Hz
70 Hz
CP. 11
oP.22
Step Frequency 1
±
409.58 Hz
0.0125 Hz
5 Hz
CP. 12
oP.23
Step Frequency 2
±
409.58 Hz
0.0125 Hz
50 Hz
CP. 13
oP.24
Step Frequency 3
±
409.58 Hz
0.0125 Hz
70 Hz
CP. 14
Pn.5
LAD load level
10…200 %
1 %
140 %
CP. 15
Pn.13
Stall level
10…200 %, off
1 %
off
CP. 16
Pn.7
Speed search condition
off, 1..15
1
8
CP. 17
uF.8
DC-voltage compensation 150...649 V, off
1 V
off
CP. 18
cn.1
Slip compensation
-2.50...2.50
0.01
0 = off
CP. 19
cn.2
Autoboost
-2.50...2.50
0.01
0 = off
CP. 20
Pn.8
DC-braking
0...9
1
7
CP. 21
Pn.11
DC-braking time
0…100
0.01 s
10 s
CP. 22
do.2
Relay output
0…24
1
2
CP. 23
Le.1
Frequency level
0...409,58 Hz
0.0125 Hz
4 Hz
Customer Parameter
Group
Change between cP-
and application
mode
Parameters of the
CP-group
Содержание COMBIVERT F4-S/1.2
Страница 1: ...C O M B I V E R T APPLICATION MANUAL Control unit F4 S 1 2 ANTRIEBSTECHNIK 00 F4 SEA K120 07 99 ...
Страница 2: ......
Страница 24: ...ru Parameter 24 ...
Страница 42: ...uF Parameter 42 ...
Страница 54: ...Fr Parameter 54 ...
Страница 58: ...An Parameter 58 ...
Страница 64: ...di Parameter 64 ...
Страница 76: ...In Parameter 76 ...
Страница 94: ......
Страница 95: ...ANTRIEBSTECHNIK ...