
Fr - Parameter
52
It is possible to copy the complete set instead of adjusting each set separately. This
means all parameter values of the target set are written over by the corresponding
parameter values of the source set. All sets 0 - 3 are possible as target sets. For
source sets, the sets 0 - 3,
def
and
init
.
def
copy the basic adjustments stored in
EPROM into the target set.
init
copies the basic adjustment into all sets, independent
from the target set. If the target set is not 0, then only the programmed parameters are
copied, since the non-programmable parameters only exist in set 0. If the source set is
neither
0
nor
def
or
init
, then only the programmed parameters can be copied.
The following limitations are valid for copying sets:
1. The default set,
def,
cannot be copied into the momentary active set. This may
only be done when the inverter is in
noP
,
LS
or
E. XX
(error).
2.
init
can only be completed with
noP
,
LS
or
E. XX
(error).
3. The source set may not be the same as the target set.
4. The target set may not be adjusted at the display of the current set
A
.
When using the keyboard the copying proces is triggered by Fr.0. Fr.0 is not visible in
Bus. The parameter value speicifies the source set. The target set is the parameter set
in which Fr.0 is edited (parameter set in the display of the parameter name). Pressing
ENTER triggers the copying process. If it could not be completed
nco
appears in the
display. This feedback must be confirmed with ENTER.
In bus the copying process is triggered by Fr.1. Fr.1 is not visible by keyboard. The
parameter value specifies the source set, the target set is specified by Fr.9.
Each parameter set can be activated in a different manner. Possible sources for the
parameter set selection are:
Parameter Value
Set Selection
0
Set selection deactivated (always set 0)
1
Set selection with Fr. 4
2
Set selection with terminal strip binary coded
3
Set selection with terminal strip input coded
In the deactive parameter set selection, the inverter always operates with the adjusted
value in set 0.
If the digital set selection is adjusted, then the set in which the inverter is operated, is
adjusted in Fr.4. The presetting can be done via keyboard as well as by Bus.
Copy Sets
(Fr. 0, Fr. 1)
Keyboard (Fr. 0)
Bus (Fr. 1)
Parameter Set
Source (Fr. 2)
Содержание COMBIVERT F4-S/1.2
Страница 1: ...C O M B I V E R T APPLICATION MANUAL Control unit F4 S 1 2 ANTRIEBSTECHNIK 00 F4 SEA K120 07 99 ...
Страница 2: ......
Страница 24: ...ru Parameter 24 ...
Страница 42: ...uF Parameter 42 ...
Страница 54: ...Fr Parameter 54 ...
Страница 58: ...An Parameter 58 ...
Страница 64: ...di Parameter 64 ...
Страница 76: ...In Parameter 76 ...
Страница 94: ......
Страница 95: ...ANTRIEBSTECHNIK ...