An - Parameter
57
ANTRIEBSTECHNIK
With offset X (An.10, An.16) and Offset Y (An.11, An.17) the zero point of the curve
can be specified. In most applications it is enough to adjust one of the two parameters.
The increase of the curve is specified by the gain (An. 9, An.15).
With these parameters a zero point hysteresis is adjusted for the analog input. Voltage
fluctuations and hum voltages at the zero point are suppressed (output of the curve
gain!).
The size can be selected by An.14 , which should be displayed by the analog output.
Parameter
Value
Process Size
Value Range
0
Actual frequency
100% = 100Hz
1
Rate of utilization
100% = 200/150/125%
2
Set frequency
100% = 100Hz
3
Output voltage
100% = max. voltage (500 V)
4
d.c. voltage
100% = 810V / 405V
5
Effective Current
100% = 2*In / 1.5 *In / 1.25 *In
6
Actual frequency
100% = 100Hz
7
Digital output
off = 0 / on = 10V
OFFSET Y
OFFSET X
GAIN
Input value
+100%
-100%
-100%
+100%
Output value
Zero Clamp
REF2 (An. 8)
Analog Out1
Function (An.14)