ru - Parameter
22
ru. 8 makes it possible to detect the peak utilization within an operating cycle. In
addition the highest value that occurs in ru. 7 is stored in ru. 8. The peak memory can
be deleted by pressing the UP or DOWN key or by bus in writing any value onto ru. 8.
When the inverter is switched off the memory is deleted.
Display of the actual apparent current (resolution of 0.1A). The resolution by bus
amounts to 0.1A.
ru.10 shows the actual active current excluding the part of the active current needed
for the stator losses. The display of ru.10 is approximately proportional to the given
torque. To maintain the correct display of the torque building active current it is
important to enter the motor parameter (dr.1... dr.5) corresponding to the rating plate.
Display of the actual dc-voltage (resolution of 1V). The highest value (drag pointer) that
occurs is stored in ru.12. ru.12 is erased by pressing UP or DOWN. The peak hold can
be deleted with bus by writing any value in ru.12. ru.12 is also erased by power on
reset of the inverter.
Display of the present output voltage (resolution of 1V).
ru.14 shows the logical condition of the input terminal. Logical interconnections, strobe
or edge triggerung are not taken into consideration.
Bit -No.
Decimal
Value
Input
Terminal
0
1
ST (Control Release)
14
1
2
RST (Reset)
14
2
4
F (Forward)
13
3
8
R (Reverse)
12
4
16
I1 (Programmed input 1)
4
5
32
I2 (Programmed input 2)
5
If an input is triggered, then the corresponding decimal value is displayed. If several
inputs are triggered, then the sum of the decimal values are displayed.
ru.15 makes it possible to control the digital outputs. It takes into consideration the
logical interconnection of the digital outputs (do. 0, do. 9 to do.25). For every active
output the corresponding decimal value is shown. If several outputs are active then the
sum of the decimal values are displayed.
Bit -No. Decimal Value
Output
Terminal
0
1
Out 1 (analog output)
10
1
2
Out 2 (Relay RLA,RLB,RLC)
1 , 2 , 3
Peak Inverter
Utilization (ru. 8)
Apparent Current
(ru. 9)
Active Current
(ru.10)
Actual DC Voltage
(ru.11, ru.12)
Output Voltage
(ru.13)
Input Terminal
State (ru.14)
Output Terminal
State (ru.15)
Содержание COMBIVERT F4-S/1.2
Страница 1: ...C O M B I V E R T APPLICATION MANUAL Control unit F4 S 1 2 ANTRIEBSTECHNIK 00 F4 SEA K120 07 99 ...
Страница 2: ......
Страница 24: ...ru Parameter 24 ...
Страница 42: ...uF Parameter 42 ...
Страница 54: ...Fr Parameter 54 ...
Страница 58: ...An Parameter 58 ...
Страница 64: ...di Parameter 64 ...
Страница 76: ...In Parameter 76 ...
Страница 94: ......
Страница 95: ...ANTRIEBSTECHNIK ...